EN779 | ASHRAE 52.2 | ISO 16890 | Width (mm) | Height (mm) | Depth (mm) | Initial Pressure Drop (Pa) | Air Flow (m3/hr) |
---|---|---|---|---|---|---|---|
G4 | MERV 8 | ISO Coarse 65% | 592 | 592 | 292 | 85 | 3400 |
G4 | MERV 8 | ISO Coarse 65% | 592 | 287 | 292 | 85 | 1700 |
Specification
Application
HVAC,AHU,Commercial buildings
Filter Frame
HIPS
Media
Activated carbon pleatable media
Max Temperature (°C)
70
Recommended Final
Pressure Drop (Pa)
450